MAN

Proizvodnja energije Diesel motorima

Operating types

  • Emergency Standby Power (ESP)
  • Limited Time Power (LTP)
  • Prime Power (PRP)
  • Continuous Power (COP)

Diesel engines for ESP

Emergency Standby Power (ESP)

  • Power output available with varying load for the duration of an emergency outage.
  • Average power output is 70% of the emergency standby power rating.
  • Typical operation is 50 hours per year with maximum expected usage of 200 hours per year
  • Standby power in accordance with ISO8528.
  • Fuel stop power in accordance with ISO 3046.

Diesel engines for LTP

Limited Time Power (LTP)

  • Power output available with varying load for the duration of the interruption of the normal source power.
  • Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year, within the following limits of maximum operating time: 100% load 50 hours per year and 90% load 200 hours per year.
  • No overload available.
  • Fuel stop power in accordance with ISO 3046.

Diesel engines for PRP

Prime Power (PRP)

  • Power output available with variable load for unlimited time. Average power output is 80% of the prime power rating.
  • With 10% overload capability for technical purposes for one hour in twelve.
  • Overload operation cannot exceed 50 hours per year.
  • Prime power in accordance with ISO 8528.
  • Fuel stop power in accordance with ISO 3046.

Diesel engines for COP

Continuous Power (COP)

  • Power output available with varying load for unlimited time. Average power output is 100% of the continuous power rating.
  • With 10% overload capability for technical purposes for one hour in twelve.
  • Continuous power is in accordance with ISO 8528.
  • Fuel stop power in accordance with ISO 3046.

Motori

  • MAN D2676LE
    MAN D2676LE
  • MAN D2862LE
    MAN D2862LE

MAN engines